Backflow Preventer Sizing Calculator

Size backflow prevention devices to protect water supplies from contamination. Calculate proper device types, sizes, and installation requirements based on hazard levels.

Application Parameters

Substances that may be dangerous to health

High Hazard (Contaminated)

Substances that may be dangerous to health

Typical Applications:

  • Chemical processing
  • Hospitals
  • Laboratories

Suitable Devices:

RPZ, DCVA

Device Comparison

Device TypeHazard LevelMin PressurePressure Loss
RPZ
Reduced Pressure Zone Assembly
high, severe30 PSI12 PSI
DCVA
Double Check Valve Assembly
medium, high25 PSI8 PSI
DCDA
Double Check Detector Assembly
medium, high25 PSI10 PSI
PVB
Pressure Vacuum Breaker
medium20 PSI5 PSI
SVB
Spill-Resistant Vacuum Breaker
low, medium15 PSI3 PSI
AVB
Atmospheric Vacuum Breaker
low10 PSI2 PSI

How Backflow Prevention Works

Protection Principles

  • Backpressure: Downstream pressure exceeds supply
  • Backsiphonage: Negative pressure in supply line
  • Check Valves: Prevent reverse flow direction
  • Air Gaps: Physical separation prevents contamination

Device Selection Factors

  • • Contamination hazard level assessment
  • • Required flow rate and pressure conditions
  • • Installation location and accessibility
  • • Maintenance and testing requirements

Backflow Preventer Sizing Formulas & Methods

Step-by-Step Sizing Process

  1. 1. Hazard Assessment: Determine contamination hazard level based on downstream connections
  2. 2. Device Selection: Select appropriate device types for hazard level
  3. 3. Flow Requirements: Calculate peak demand flow rate (GPM)
  4. 4. Pressure Analysis: Account for elevation losses and device pressure drop
  5. 5. Size Verification: Ensure device capacity meets flow and pressure requirements
  6. 6. Residual Pressure: Verify adequate downstream pressure for fixture operation

Pressure Loss Calculations

Total Pressure Loss:

P_loss = P_device + P_elevation + P_fitting

Where P_device = manufacturer's rated pressure drop

Elevation Pressure Loss:

P_elevation = 0.433 × height(ft)

0.433 PSI lost per foot of vertical rise

Residual Pressure:

P_residual = P_supply - P_loss

Must be ≥20 PSI for adequate fixture operation

Device Selection Matrix

Low Hazard (Potable Water):

AVB, SVB acceptable

Minimal pressure loss, basic protection

Medium Hazard (Non-Potable):

PVB, DCVA, SVB required

Dual check valves or air gap protection

High/Severe Hazard:

RPZ assembly mandatory

Maximum protection with relief valve

Flow Rate Sizing Guidelines

Residential Applications:

Peak demand = 10-15 GPM typical

Size device for 120% of peak

Consider simultaneous fixture use

Commercial Buildings:

Use fixture unit method

Apply diversity factors

Include process loads

Industrial/Irrigation:

Size for actual system demand

Include safety factor (10-25%)

Consider continuous operation

Variable Definitions & Standards

P_supply = Upstream pressure (PSI)

P_device = Device pressure loss (PSI)

P_elevation = Elevation loss (PSI)

Q = Flow rate (GPM)

Height = Vertical rise (ft)

P_residual = Downstream pressure (PSI)

GPM = Gallons per minute

PSI = Pounds per square inch

Min Residual: 20 PSI (typical)

Max Velocity: 8 ft/sec

Code Standards: USC, IPC, UPC

Test Frequency: Annual

Device Performance & Pressure Loss Data

Typical Pressure Loss by Device Type

Low Pressure Loss Devices

  • AVB: 2-3 PSI typical
  • SVB: 3-4 PSI typical
  • PVB: 5-7 PSI typical

Higher Protection Devices

  • DCVA: 8-12 PSI typical
  • DCDA: 10-15 PSI typical
  • RPZ: 12-20 PSI typical

Installation Requirements by Device Type

RPZ Assemblies

  • • Test cocks required
  • • Drain line mandatory
  • • 12" minimum clearance
  • • Frost protection needed
  • • Annual testing required

DCVA/DCDA

  • • Test cocks required
  • • No drain line needed
  • • 6" minimum clearance
  • • Shutoff valves both sides
  • • Annual testing required

PVB/SVB/AVB

  • • No test cocks needed
  • • Visual inspection access
  • • Above highest outlet (PVB)
  • • No backpressure allowed
  • • Annual inspection

Backflow Preventer Sizing Questions & Answers

How do I determine what hazard level to select?

Look at what's actually connected to your water system. If it's just potable water fixtures (sinks, drinking fountains), that's low hazard. Non-potable but not harmful stuff like irrigation or cooling towers is medium hazard. High hazard means chemicals, medical equipment, or anything that could make people sick. Severe hazard is toxic, radioactive, or lethal substances. When in doubt, go with the higher hazard level - it's better to be safe.

Why does the calculator recommend RPZ for everything high hazard and above?

Because RPZ assemblies provide the highest level of protection. They have two check valves plus a relief valve that opens if the zone between them gets pressurized, which means contamination can't flow back even if both check valves fail. For high and severe hazard applications, you really can't afford to have any backflow events, so the extra protection is worth the higher cost and pressure loss.

What does "residual pressure" mean and why does it matter?

Residual pressure is what's left over after the backflow preventer drops the pressure. You need at least 20 PSI downstream for most fixtures to work properly. If the calculator shows low residual pressure, your fixtures won't get adequate flow, or worse, you might not have enough pressure for the backflow preventer to work correctly. You might need a booster pump or larger device to fix this.

Should I include building height even if the backflow preventer is at ground level?

Yes, absolutely. The calculator needs to know the total elevation difference because you lose about 0.43 PSI for every foot of elevation. Even if your backflow preventer is at ground level, if you're serving fixtures on upper floors, that elevation loss affects your available pressure. The calculator uses this to make sure you have enough pressure at the highest fixtures.

What's the difference between all these device types (RPZ, DCVA, PVB, etc.)?

Think of them as different levels of protection. AVB is basic protection for low-risk stuff. PVB works for irrigation but can't handle backpressure. DCVA has two check valves for better protection. RPZ is the gold standard with two check valves plus a relief valve. Each step up gives more protection but costs more and loses more pressure. The hazard level determines which types are acceptable.

Why does the calculator sometimes suggest a larger size than my pipe?

Because backflow preventers have built-in pressure loss, and sometimes you need a bigger device to get the flow rate you need without losing too much pressure. It's like putting a smaller nozzle on a garden hose - you get higher velocity but lower flow. A larger backflow preventer might have lower pressure loss even though it's bigger than your pipe. You can always reduce down to your pipe size after the device.

Do I really need annual testing, and who can do it?

Yes, it's required by code for RPZ and DCVA assemblies, and it's a good idea for all devices. You need a certified backflow tester - not just any plumber. They have special equipment to test the check valves and relief valve operation. If the device fails, it needs immediate repair or replacement. Some water utilities track this and will shut off your service if you don't comply.

What happens if I choose a device that's too small for my flow rate?

You'll get inadequate flow to your fixtures, and the device might not operate properly. Backflow preventers are designed to work within their flow ratings. Push them too hard and the pressure drop increases dramatically, check valves might not seat properly, and you could actually reduce the protection level. It's always better to size up rather than try to squeeze maximum flow through an undersized device.

Can I install a bypass around the backflow preventer for maintenance?

Only where specifically allowed by local code, and even then it's usually restricted to low-hazard applications. Most codes prohibit bypasses for medium hazard and above because people forget to close them or use them improperly. If a bypass is allowed, it typically requires a separate backflow preventer on the bypass line. When in doubt, don't install a bypass.

What should I do if the calculator says my system isn't code compliant?

Usually it means you don't have enough pressure after the device pressure loss. Your options are: increase supply pressure (booster pump), use a larger device with lower pressure loss, reduce the flow demand, or sometimes relocate the device to a lower elevation. Don't ignore this warning - insufficient pressure means poor fixture performance and potentially compromised backflow protection.

How much do backflow preventers typically cost to install?

Basic residential RPZ assemblies run $300-$800 plus installation, which can be another $500-$1,500 depending on pipe work needed. Commercial installations often hit $2,000-$10,000+ for larger units with testing requirements. Don't forget annual testing costs ($100-$300) and repairs when check valves fail. It's expensive, but way cheaper than contaminating the water supply and dealing with lawsuits.